As of October 28, 2026, the energy code in force in Hillsborough, Pinellas and Pasco counties is the Florida Building Code, Energy Conservation, 8th Edition (2023), which took effect December 31, 2023. For a new home or an addition in Climate Zone 2A, its prescriptive table asks R-38 in the ceiling, R-13 in wood-frame walls, R-4 or R-6 in concrete-block walls, R-13 in raised floors and R-0 under a slab. Those are minimums for new homes and major renovations. They are not a rule for an existing attic: adding insulation to an existing attic is your choice, and the code does not require it.
Florida’s 9th Edition (2026) code is scheduled to take effect December 31, 2026. None of its values are quoted below, because the Florida Building Commission’s October 2026 workplan still showed its final hearing and publication as unscheduled.
Every code statement below is as of October 28, 2026, and every figure comes from the Commission’s own documents, the energy code’s Form R402, the Florida Statutes or another source named beside it, all opened on October 28 and 29, 2026; the list near the end shows where to check each one. The building official in your county or city decides how the code applies to a particular project.
Which Florida energy code applies in 2026?
The Commission’s home page states the date in one line: “The Effective Date for the Florida Building Code, 8th Edition (2023), is December 31, 2023.” Florida’s code is statewide: counties do not write their own energy code, so the same edition governs in all three counties.
The next edition is the 9th Edition (2026). The Commission’s workplan for it, dated October 2026, gives the effective date as “12/31/2026,” six months after publication. It lists the final rule hearing, the filing with the Secretary of State and the final published code as “TBD,” and it quotes the statute that an updated code “shall take effect no sooner than 6 months after publication of the updated code.” So the date is scheduled, not settled, and until the 9th Edition takes effect the 8th Edition numbers below are the ones in force.
What climate zone are Hillsborough, Pinellas and Pasco counties in?
All three are Climate Zone 2A. The energy code lists every Florida county in a climate-zone table: the number picks the row of the insulation table, the letter A means moist, and an asterisk marks a warm-humid county. The International Code Council’s published sample pages of the 7th Edition (2020) list “2A Hillsborough*,” “2A Pasco*” and “2A Pinellas*.” Florida’s insulation table has one row for each of the state’s two climate zones, and Tampa Bay uses the Zone 2 row.
Our county pages cover each county’s housing and utilities: Hillsborough County, Pinellas County and Pasco County.
What R-value does the Florida energy code require in a new home?
R-value measures how well insulation resists heat flowing through it, and ENERGY STAR says the higher the R-value, the better the thermal performance. The simplest way to comply with the code is the prescriptive path. Form R402, the prescriptive form in Appendix RD of the 8th Edition, says the building “must meet or exceed all of the energy efficiency requirements and applicable mandatory requirements summarized on this form.” For Climate Zone 2 the form’s table and notes ask:
- Ceiling: R-38.
- Wood-frame walls: R-13.
- Concrete-block (mass) walls: R-4 or R-6. The form’s footnote reads: “The second R-value applies when more than half the insulation is on the interior of the mass wall.” So R-6 applies when more than half the insulation is inside the block, and R-4 when it is not.
- Raised floors: R-13, meaning a framed floor over a crawl space or open piers. Slab, basement wall and crawl-space wall: R-0.
- Windows: a maximum U-factor of 0.40 (lower is better) and a maximum solar heat gain coefficient (SHGC) of 0.25, with impact-rated windows allowed up to U-0.65 in Zone 2 under the form’s footnote 3. Skylights are held to U-0.65.
- Air leakage: a blower-door result of no more than 7 ACH50, explained below.
- Ducts: R-8 insulation on ducts 3 inches and larger in an unconditioned attic, R-6 on smaller attic ducts, and a limit on duct leakage, also below.
The form says how to read those numbers. R-values are minimums, and U-factors and SHGC are maximums. For the ceiling, walls and floors it asks for the lowest R-value to be installed, not an average, while windows and skylights may be area-weighted averages. If insulation goes into a cavity thinner than its label thickness, the installed R-value, not the label, has to meet the table. And for the wall rows the R-values are “for insulation material only as applied in accordance with manufacturer’s installation instructions,” so the block in a block wall does not count toward its R-4 or R-6.
The code’s R-38 for a new ceiling is a thickness as well as a number. At the per-inch figures we work from for spray foam, open-cell at R-3.9 to R-4.2 per inch and closed-cell at R-6.9 to R-7.1, R-38 is about 9 to 10 inches of open-cell or about 5.4 to 5.5 inches of closed-cell. For blown-in fiberglass or cellulose the depth depends on the product, so any insulation quote, for a new house or an old one, should state both the R-value and the depth.
ENERGY STAR’s numbers are different, and they are advice, not code. For retrofitting an existing wood-framed house in its Zone 2, ENERGY STAR recommends R-49 in an uninsulated attic, R-38 on top of 3–4 inches of existing insulation and R-13 in floors. Its table is based on the 2021 International Energy Conservation Code, the national model code. A Florida Solar Energy Center (FSEC) draft interim report to the state, dated October 15, 2023, notes that the 2021 model code raised its Zone 2 ceiling minimum from R-38 to R-49 while Florida’s 8th Edition kept R-38. So R-38 is the prescriptive minimum for new construction, ENERGY STAR’s figures are targets to measure an existing attic against, and neither is a requirement on an existing house.
What does the code ask of ducts, air sealing and the blower-door test?
Ducts
The U.S. Department of Energy’s Building America duct guide (2004) takes the attic as the typical Florida duct location and says typical systems with ducts in attics or crawl spaces lose from 25% to 40% of the heating or cooling energy that passes through them. For a new home or an addition, Form R402 asks R-8 insulation on ducts 3 inches and larger in an unconditioned attic and R-6 on attic ducts under 3 inches; for ducts in other unconditioned spaces it asks R-6 (3 inches and larger) or R-4.2 (smaller). Total duct leakage is limited to 4 cfm (cubic feet of air per minute) per 100 square feet of conditioned floor area when the air handler is installed and 3 when it is not. No test is required when all the ducts and the air handler are inside the thermal envelope (the boundary around the conditioned space).
The form has one more rule about where equipment goes. On the prescriptive path for new work it says “Air handling units are not allowed in attics”; FSEC’s 2023 draft review lists it as a prescriptive-compliance rule (R403.3.6), and the performance path is separate. It is a design rule for new work on the prescriptive path, not a rule about an air handler already in an existing attic: an existing house comes under the energy code only in the cases set out below. Form R402 says duct testing is done by individuals named in sections 553.993 and 489.105 of the Florida Statutes. We seal ducts; air handler work and replacing ducts belong to an air-conditioning contractor, and we say so at the estimate.
Air sealing and the 7 ACH50 blower-door test
A new home is tested for air leakage. Form R402 says a blower-door test is required on the building envelope to verify leakage of no more than 7 ACH50, and the report must reach the code official before the certificate of occupancy is issued. ACH50 counts how many times the house’s air would be replaced in an hour at a test pressure of 50 pascals. The Department of Energy describes a blower door as a temporary barrier over an open outside doorway with a fan that applies a small pressure to the house, used mainly to test for air leakage.
Three details come with the test. A house that tests below 3 ACH50 needs whole-house mechanical ventilation, which the Department of Business and Professional Regulation (DBPR), in its brochure BLDG-124 on what changed in the 8th Edition, says the code clarifies is “required for dwelling units with air leakage rates less than 3 ACH50.” The form says the testing exception “may apply for additions, alterations, or renovations.” And an attic sealed at the roof deck is counted in the test, as the sealed-attic section below explains.
The form lists other mandatory air-sealing items. Its air leakage row says the envelope is “to be caulked, gasketed, weatherstripped or otherwise sealed” per Table R402.4.1.1; recessed lights have to be IC-rated, meaning rated for contact with insulation, and tested at no more than 2.0 cfm. Insulation and air sealing work as one system. If a quote specifies a depth of insulation and never mentions air sealing, it is half a job. Our air sealing comes first, and the depth follows.
Can a new house meet the code another way?
Yes. Form R402 itself says that a building that does not comply with its method “may still comply under Section R405 or R406.” R405 is the simulated performance path: approved compliance software compares the proposed house with a standard reference house, and the house passes when its total e-Ratio, its modeled energy loads divided by the reference house’s, is 0.95 or less, which DBPR says made the performance path 5% stricter than in the 7th Edition. R406 is the Energy Rating Index path. On these paths a weak number in one place can be traded for a strong one somewhere else; FSEC’s review of the code refers to such exchanges as trade-offs.
On the performance path, the code counts a radiant barrier or a cool roof as a credit; neither is on the prescriptive form. The code lists installation criteria for them under section R405.7, and DBPR says the 8th Edition raised the operative surface emissivity limit for sheet radiant barriers from 0.06 to 0.10. Emissivity is how much heat a surface gives off, and FSEC’s radiant barrier guide says the lower the better. FSEC’s 2023 draft review lists a minimum ceiling insulation level of R-19 on the performance path, space permitting (R405.2.1). Our radiant barrier guide covers whether one is worth it, and we install radiant barriers.
Does an existing house or attic have to meet the Florida energy code?
Only in particular cases, as of October 28, 2026. Code section R101.4.2 says the buildings exempt from the Energy Conservation volume “include existing buildings except those considered renovated buildings, changes of occupancy type or previously unconditioned buildings to which comfort conditioning is added.” The Building Officials Association of Florida (BOAF) prints that section in its interpretation 8860, published January 8, 2024, together with the code’s definition: a renovated building is “a residential or nonresidential building undergoing alteration that varies or changes insulation, HVAC systems, water heating systems or exterior envelope conditions, provided the estimated cost of renovation exceeds 30 percent of the assessed value of the structure.” BOAF interpretations are non-binding, and this one was written about air-conditioning equipment changeouts, but the exemption it quotes is the code’s own.
That is why a stand-alone job to add insulation to an existing attic is not forced by the code. What changes the picture is a renovation whose estimated cost passes 30% of the structure’s assessed value, a change of occupancy, or a previously unconditioned building that gets comfort conditioning for the first time. The building official decides whether a particular project crosses the 30% line.
An addition is different. Form R402’s scope names “additions to existing residential buildings,” so a new room added to the house is held to the new-construction numbers above. The same sentence lists alterations and renovations “as applicable,” which for an existing house means only the three cases above. If you want to know where your own attic stands, our attic insulation guide shows how to measure it against ENERGY STAR’s levels.
Does reroofing trigger the energy code?
As of October 28, 2026, reroofing alone generally does not trigger a new insulation requirement under Florida’s energy code; your building department has the final word. Whether a roof job inside a larger remodel counts toward the 30% line is a question for the building official.
If the roof deck itself is being replaced, FSEC’s radiant barrier guide (2005) says that is a good time to consider a radiant barrier, especially foil-faced roof sheathing. That is a roofing-and-attic decision, not a code requirement.
Is spray foam on the roof deck allowed by Florida code?
Yes, under conditions. As of October 28, 2026, Florida’s residential code allows a sealed, or unvented, attic in section R806.5, and a state statute adds an energy-code route for new homes.
What R806.5 says
The Commission staff’s analysis of declaratory statement DS 2026-030 quotes the 8th Edition text: unvented attics “shall be permitted where all the following conditions are met.” The analysis quotes the first four, not the whole section. The attic space has to be completely within the building thermal envelope. No interior Class I vapor retarder, the most vapor-tight class, may be installed on the ceiling side. Where wood shingles or shakes are used, a minimum 1/4-inch vented airspace has to separate them from the roofing underlayment. And in Climate Zones 5, 6, 7 and 8, air-impermeable insulation has to be a Class II vapor retarder, a rule that does not apply in Florida. R806.5 settles whether an attic may be unvented; the building official decides how the rest of the code applies to a job.
The statute’s R-20 route
Section 553.9065 of the Florida Statutes, effective July 1, 2025, says unvented attic and unvented enclosed rafter assemblies “insulated and air sealed with a minimum of R-20 air-impermeable insulation” meet section R402 of the 8th Edition if all four of these apply. The house tests under 3 ACH50. It has a positive input ventilation system or a balanced or hybrid whole-house mechanical ventilation system. Exposed roof rafters not already covered by the R-20 get at least R-3 air-impermeable insulation, unless a finished ceiling covers them directly or continuous insulation sits above the roof deck. And all indoor heating, cooling and ventilation equipment and ductwork is inside the building thermal envelope. Read it as a way for a new house to comply, not as a rule for retrofits; the statute does not say it applies to existing houses, it names the 8th Edition, and it does not say how it will read once the 9th Edition takes effect. At the R-values per inch above, R-20 is about 4.8 to 5.1 inches of open-cell foam or about 2.8 to 2.9 inches of closed-cell.
Blower door, ducts and moisture
For the blower-door test, DBPR says that if an attic is both air sealed and insulated at the roof deck, the access doors and hatches between the house and the attic are opened and the attic’s volume is added to the conditioned volume. For the ducts, the staff analysis concluded that R806.5 does not require dedicated supply and return vents in an unvented attic, and it quotes BOAF interpretation 9545, which calls cooling ducts there “optional and up to the designer” and adds that “some designers provide conditioning to this space to reduce humidity which can occur, but this is optional.”
A December 2024 Florida Solar Energy Center review for the state found mixed results on moisture and energy use in sealed attics; the Florida research it found covered open-cell foam only, and the studies from hot-humid climates agreed that roof-wood moisture stayed at acceptable levels with open-cell foam on the roof sheathing. That is a finding about studies, not a promise for any one roof. The review’s simulations in Miami and Tallahassee found “some increase in energy use” on the statute’s minimal R-20 route in “many but not all simulated homes.” Neither the code nor the statute promises a dry attic, and a sealed attic may still need its humidity managed. Our sealed attic guide goes further into moisture, the roof and cost, and our open-cell and closed-cell foam page compares the two foams.
What does the code ask of a concrete block wall?
The block-wall numbers above, R-4 or R-6 by the footnote, are for new construction. The form counts insulation material only, so on the prescriptive path a block wall with nothing added does not meet the table by itself. Nothing in the table requires an existing block wall to be insulated, and the renovated-building rule above is what decides whether a remodel brings an existing wall under the code. Where insulation goes on a block wall, inside or outside, is in our concrete block wall insulation guide.
What the code does not tell you: savings and the attic
The code sets minimums; it does not estimate savings. ENERGY STAR does, as a modeled average. For air sealing plus attic and floor insulation brought up to 2012 International Energy Conservation Code levels in a typical 1970–1989, 1,700-square-foot wood-frame house, its Climate Zone 2 estimate is 6% of total energy costs and 9% of heating and cooling costs, and it says savings are higher in the North than in the South. That is an average from a model, not a forecast for any one Tampa Bay house.
FSEC’s radiant barrier guide (2005) shows the attic, including heat gain to the ducts, as 22% of the total cooling load in a typical 1,500-square-foot Central Florida home, which is why Tampa Bay insulation work starts overhead. The utility rebates are separate from the code and have R-value rules of their own. If your electric bill says Tampa Electric, Tampa Electric’s ceiling insulation rebate applies; if it says Duke Energy, Duke’s attic insulation rebate applies. Withlacoochee River Electric does not list an insulation rebate. The details are in our Tampa Bay insulation rebate guide. There is no federal homeowner tax credit for insulation installed in 2026, and a contractor still advertising one is wrong; the insulation tax credit guide has the detail.
Permits, termites and the hurricane zone
Permit rules vary by county and city; ask your building department, or ask us when we quote.
Florida requires termite protection on new homes, and foam should not touch the soil outside.
The High-Velocity Hurricane Zone, the part of the Florida Building Code that holds South Florida’s strong hurricane provisions, covers Miami-Dade and Broward counties only, as of October 28, 2026. No Tampa Bay county is in it. Wind provisions sit in the Building and Residential volumes of the code, not the energy volume.
What insulation costs in Tampa Bay
The code sets R-values, not prices. Most of our projects run between $3,500 and $12,500. The house sets the number: the size and depth of the attic, how much old insulation is in the way, whether the air handler and ducts sit in the attic, and whether the job is depth on the attic floor or a sealed attic with foam at the roof deck. Closed-cell foam costs more per inch, mainly because it uses more material, and reaches a given R-value in less thickness. The insulation cost guide and the spray foam cost guide break the numbers down by project.
How to check this yourself
All opened on October 28 and 29, 2026; where a document shows its own date, it is given. Each source is named by publisher and site:
- The 8th Edition’s effective date and the 9th Edition workplan (October 2026): the Florida Building Commission, floridabuilding.org home page and October 2026 workplan. The county climate-zone sample pages of the 7th Edition: the International Code Council, 7th Edition sample, shop.iccsafe.org.
- Form R402-2023, Appendix RD of the 8th Edition, as posted on the Putnam County and Seminole County websites.
- DBPR brochure BLDG-124 on what changed in the 8th Edition, and FSEC’s reports to DBPR (a draft interim report of October 15, 2023 and a final report revised December 6, 2024), floridabuilding.org.
- BOAF interpretation 8860 (January 8, 2024), interpretations.boaf.net; the Commission staff analysis of declaratory statement DS 2026-030, floridabuilding.org; Florida Statutes section 553.9065 (2026 edition), flsenate.gov; and Laws of Florida chapter 2024-191, section 7 (the July 1, 2025 effective date), laws.flrules.org.
- ENERGY STAR, Recommended Home Insulation R-Values and Methodology for Estimated Energy Savings, energystar.gov.
- FSEC-EN-15, Radiant Barriers (2005), fsec.ucf.edu; DOE Building America, Better Duct Systems for Home Heating and Cooling (2004) and Improving the Efficiency of Your Duct System, energy.gov; the IRS Energy Efficient Home Improvement Credit page, irs.gov.
- The hurricane zone: the Commission’s wind-load fact sheet for the 7th Edition (June 2020) and its other code documents, floridabuilding.org.
Common questions about the Florida energy code and insulation
Does my existing attic need to reach R-38?
No. R-38 is the prescriptive ceiling minimum in the Florida energy code (8th Edition, 2023) for new homes and additions in Climate Zone 2. Adding insulation to an existing attic is your choice; the code does not require it. As of October 28, 2026, an existing house comes under the code only as a renovated building (estimated cost over 30% of the assessed value of the structure), a change of occupancy, or a previously unconditioned building to which comfort conditioning is added; an addition is held to the new-construction numbers.
What R-value does the Florida energy code require for a new house?
For a new home in Hillsborough, Pinellas or Pasco County (Climate Zone 2A), the 8th Edition prescriptive table asks R-38 in the ceiling, R-13 in wood-frame walls, R-4 or R-6 in concrete-block walls, R-13 in raised floors and R-0 under slabs. Ducts in an unconditioned attic need R-8 if they are 3 inches or larger, and the house must test at 7 ACH50 or less. These figures are as of October 28, 2026.
Does a new roof mean new insulation?
As of October 28, 2026, reroofing alone generally does not trigger a new insulation requirement under the Florida energy code; your building department has the final word. The code reaches an existing house as a renovated building, a change of occupancy or a previously unconditioned building to which comfort conditioning is added, so a roof job inside a larger remodel is a question for the building official.
Is spray foam on the roof deck legal in Florida?
Yes, under conditions. As of October 28, 2026, section R806.5 of the Florida residential code permits an unvented attic when conditions are met, including that the attic is completely inside the building thermal envelope and no Class I vapor retarder is installed on the ceiling side; the Class II vapor retarder rule applies only in Climate Zones 5 through 8. Florida Statutes section 553.9065 adds an energy-code route for new construction with at least R-20 air-impermeable insulation when the house tests under 3 ACH50, has a positive input or a balanced or hybrid whole-house mechanical ventilation system, has at least R-3 air-impermeable insulation on exposed rafters unless a finished ceiling covers them directly or continuous insulation sits above the roof deck, and has all indoor heating, cooling and ventilation equipment and ductwork inside the thermal envelope. Neither promises a dry attic.
What does 7 ACH50 mean?
ACH50 is air changes per hour at a blower-door test pressure of 50 pascals. As of October 28, 2026, the 8th Edition energy code requires a new home to test at 7 ACH50 or less, with the report going to the code official before the certificate of occupancy. A home that tests under 3 ACH50 must also have whole-house mechanical ventilation. A testing exception may apply for additions, alterations or renovations.
Do I need a permit to add attic insulation?
Permit rules vary by county and city; ask your building department, or ask us when we quote.
What does the code say about concrete block walls?
As of October 28, 2026, the 8th Edition prescriptive table asks R-6 for a concrete-block (mass) wall in a new home when more than half the insulation is on the interior of the wall, and R-4 otherwise. The R-value counts the insulation material only, not the block. The table applies to new construction. Nothing in it requires an existing block wall to be insulated.
When does the Florida energy code change?
As of October 28, 2026, the 8th Edition (2023) is in force and the 9th Edition (2026) is scheduled to take effect December 31, 2026. The Commission workplan dated October 2026 still lists the final rule hearing and publication as to be determined, and the law says an updated code takes effect no sooner than 6 months after publication, so the date can move. The 9th Edition values are not final, so none are given.
What climate zone is Tampa Bay in?
Climate Zone 2A. As of October 28, 2026, the Florida energy code county table lists Hillsborough, Pinellas and Pasco counties as 2A, each with the asterisk that marks a warm-humid county. Tampa is in Hillsborough County, St. Petersburg and Clearwater are in Pinellas County, and New Port Richey and Wesley Chapel are in Pasco County. The zone selects the Zone 2 row of the prescriptive insulation table.
Free estimate in Tampa Bay
Our free estimate is our own visit to the house, separate from any utility program and from the building department. It is not a code inspection and it does not open a rebate. We look at the depth and condition of what is in the attic, the top of the block walls and the other places air gets in, where the air handler and ducts sit, and any sign of moisture, and you get the scope, the materials, the R-values and depths, and the price in writing.
We install open-cell and closed-cell spray foam, blown-in attic insulation in fiberglass or cellulose, fiberglass batts and rigid foam board, and we air seal. We also install radiant barrier, remove old insulation, clean up attics and seal ducts. Air handler work and replacing ducts belong to an air-conditioning contractor, and we say so at the estimate.
Call 914-554-2289 or use the contact form. Our Florida branch covers Hillsborough, Pinellas and Pasco counties. The Home Insulators is a family-owned company that has been insulating homes in the Northeast since 2015. Our own crew does the work and we never subcontract it.
Learn more
- Insulation contractors across Tampa Bay, by county and town
- Attic insulation in Florida: depth, type and lower AC bills
- Sealed attics: spray foam on the roof deck
- Insulating concrete block walls
- Radiant barrier in Tampa Bay: is it worth it?
- Tampa Electric and Duke Energy insulation rebates
- Spray foam insulation cost
- Is there still a tax credit for insulation?